Example 3: design of rectangular beam
design rectangular sections for the beams, loads, and ρ values shown. Beam weights are not included
in the loads shown. Assume concrete weighs 150 lb/ft3 , fy= 60,000 psi, and fc'= 4000 psi, unless given otherwise.
in the loads shown. Assume concrete weighs 150 lb/ft3 , fy= 60,000 psi, and fc'= 4000 psi, unless given otherwise.
Figure 1
first, we will calculate the ultimate load, we have point live load and distributed dead load, therefore will take each load separately
ultimate live load=1.6*PL=1.6*20=32k
assuming the weight of beam=0.50k/ft
dead load=2+0.5=2.5 k/ft
ultimate dead load=1.2*2.5=3.00k/ft
Mu from moment diagram in figure 1=657.5k-ft=7,890,000lb-in
Figure 1
Mu=Ф*Mn=Ф*Asfy(d-a/2)
Mu/(b*d^2)=Ф*ρ*fy(1-fy*ρ/1.7*fc')
ρ=0.18*4,000/60,000=0.012
bd^2=Mu/(Ф*ρ*fy(1-fy*ρ/1.7*fc') assuming Ф=0.90
Mu=7,890,000lb-in
bd^2=7,890,000/(0.9*.012*60,000*(1-60,000*0.012/1.7*4000))=13,617.88
taking bd= 16x29.5
using 16*33 as beam dimension (bxh)
checking beam weight=16*33*150/144=0.55k/ft not ok
then calculating ultimate dead load again
dead load=2+0.55=2.55 k/ft
ultimate dead load=1.2*2.55=3.06k/ft
Mu=664.25 k-ft=7,971,000lb-in
bd^2=7,971,000/(0.9*.012*60,000*(1-60,000*0.012/1.7*4000))=13,757.61
bd= 16x29.5 is ok
As=ρ*b*d=0.012*16*29.5=5.664in2
using 4#11=4*1.56=6.24 in2 ok
checking for Ф=0.9 or no
(εt+0.003)/(d)=0.003/c
C=a/β1
β1=0.85 for fc'=4000 psi or less
a=Asfy/(0.85*fc'*b)
a=6.24*60,000/(0.85*4000*16)=6.88in
C=a/β1=6.88/0.85=8.1in
εt=0.003*(29.5)/8.1-0.003=0.0079>0.005 so section is tension control Ф=0.9 is ok
checking for ρmin
As,min=(3√fc'/fy)*bw*d and not less than 200bw*d/fy
As,min=3*√4000*16*29.5/60,000 and not less than 200*29.5*16/60,000
As,min=1.49 in2 and not less than 1.57in2 ok, our As is larger than the minimum
checking Ф*Mn>Mu
Ф*Mn=0.9*6.24*60,000(d-a/2)
Ф*Mn=0.9*6.24*60,000(29.5-6.88/2)=8,781,177.6lb-in> Mu ok
Comments
Post a Comment